TEDAŞ-MLZ/2002–043.B 24 / 110 VDC 50–1000 A

Fault indicator (AGD)

A device that detects faults in electrical or electronic systems and notifies the user. It measures phase currents from three current transformers connected to underground network cables and calculates the earth current.

Fault indicator (AGD)
Fault indicator (AGD)
Operating principle

Detects phase and earth faults separately

It measures phase currents from three current transformers connected to underground network cables and calculates the earth current. If the measured phase current exceeds the threshold for the set duration, a fault is detected.

When a fault is detected, the display shows which phases or the earth are affected. In all fault conditions, the fault indicator flashes and the contacts operate. If the fault clears before the automatic reset time expires and stays clear for 3 seconds, the device returns to normal.

Real-time current monitoring

Monitors three-phase currents in real time and accurately calculates and detects earth faults.

Flashing visual alert

Gives a flashing visual alert and operates the contacts in case of a fault.

Automatic reset

Adjustable current and time thresholds with automatic return to normal operation.

Fault log

Stores the last 100 faults in real time with day/month/year information.

Technical data

Specification values andkey features

Technical specifications

Operating voltage
24 VDC / 110 VDC
Phase current threshold
50 – 1000 A
Earth current threshold
20 – 700 A
Fault detection time
40 – 500 ms
Number of fault records
100 records
Specification
TEDAŞ-MLZ/2002–043.B

Key features

  • Monitors three-phase currents in real time
  • Accurately calculates and detects earth faults
  • Offers adjustable current and time thresholds
  • Indicates phase and earth faults separately
  • Gives a flashing visual alert on fault
  • Provides relay contact output for alarm and remote monitoring
  • Can return to normal operation with automatic reset
  • Designed for underground cable networks
  • Reliable operation with low maintenance requirements
  • Suitable for industrial and distribution networks
  • Stores the last 100 fault records in real time with dates in day/month/year format

Values are shared for information purposes and may vary. Production with different values is possible. For details, contact us.

From the same category

Relatedproducts

Rectifiers and MV equipment category

Is this product right for your project?

Let’s evaluate your installed power, site conditions and specification requirements together.